Single element canister style with service indicator
Aspiration
TA
Fuel System
Mechanical unit injection
Bore
7 in
Displacement
4,211 in³
Stroke
7 in
Air Inlet
Single element canister style with service indicator
Exhaust Flange Size
203.2 mm (8.0 in)
Generator Set Specifications
Minimum Rating
1450 ekW
Maximum Rating
1750 ekW
Voltage
380 to 13800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Continuous, Prime, Standby, Mission Critical
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Duty Cycle
Continuous, Prime, Standby, Mission Critical
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Standby Rating
1750 ekW
Prime Power Rating
1600 ekW
Generator Set Dimensions
Height - Maximum
95 in
Length - Maximum
247 in
Width - Maximum
90 in
Dry Weight - Genset (maximum)
28,840 lb
Cat Generator Set Package
Cat generator set packages have been fully prototype tested
Accepts 100% block load in one step and meets NFPA 110 loading requirements
Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
Reliable, rugged, durable design
Field-proven in thousands of applications worldwide
Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
Superior motor starting capability minimizes need for oversizing alternator
Designed to match performance and output characteristics of Cat diesel engines
Robust Class H insulation
EMCP 4 Control Panel
User-friendly interface and navigation
Scalable system to meet a wide range of installation requirement
Expansion modules and site-specific programming for specific customer requirements
Cooling System
Designed to operate in standard ambient temperatures up to 50°C (122°F)
Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
UL 2200 Listed
CSA
IBC seismic certification
OSHPD pre-approval
One Safe Source
Components used in the generator set are selected at the design stage to provide optimum package performance
The generator set is fully assembled at a Caterpillar facility following our quality guidelines
Each generator set package is tested before leaving the Caterpillar facility
Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
Cat dealers have over 1,800 dealer branch stores operating in 200 countries
Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Air Inlet System
Air cleaner; single element canister type
Control Panels
Accessory module data link
Low coolant level
Environmental sealed front face
EMCP 4.2B
6 Customer programmable digital inputs
Communications:
Load histogram feature
Overspeed
Alarm acknowledge
kW-hr (total)
24 Volt DC operation
Over/under voltage (27/59)
1 programmable relay outputs (Form C)
kVAr-hr (total)
Emergency stop pushbutton
PLC functionality
Speed adjust
Lamp test
Auto/start/stop control
Over/under frequency (81 o/u)
Generator phase sequence
Revers Power (kW) (32)
Oil pressure (psi, kPa or bar
Coolant temperature
RPM
Overcurrent (50/51)
IVR includes reactive droop capability, 3-phase voltage sensing,
KVAR / PF modes, RFI suppression, min / max exciter.
Limiter and exciter diode monitor