D600 GC (60 Hz) Generator Set

  • Exterior View
  • Interior View

D600 GC (60 Hz) Generator Set

Minimum Rating 600 ekW
Maximum Rating 600 ekW
Emissions/Fuel Strategy EPA Stationary Emergency
Voltage 480 to 600 Volts
Frequency 60 Hz
Speed 1800 rpm
Generator Set Specifications
Minimum Rating 600 ekW
Maximum Rating 600 ekW
Emissions/Fuel Strategy EPA Stationary Emergency
Voltage 480 to 600 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby
Engine Specifications
Engine Model Cat® C18 In-line 6, 4-cycle Diesel
Bore 6 in
Stroke 7 in
Displacement 1,106 in³
Compression Ratio 14.5:1
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel System MEUI
Governor Type ADEM™A4
Generator Set Dimensions
Length - Maximum 196 in
Width - Maximum 73 in
Height - Maximum 101 in
Height - Minimum 79 in
Dry Weight - Genset (minimum) 8,960 lb
Dry Weight - Genset (maximum) 11,647 lb

Cat Generator Set Package

Cat Diesel Engine

SR500 Alternator

GCCP 1.2 Control Panel

Cooling System

Certifications

One Safe Source

World Wide Product Support

  • Air Inlet System
    • Turbocharger
    • Air cleaner - Non-Canister, Disposable
    • Aftercooler core
  • Control Panel
    • GCCP 1.2
  • Cooling System
    • Radiator sight gauge
    • Thermostats and housing.
    • Coolant drain valve.
    • Jacket water pump, gear driven, centrifugal
    • Blower fan and fan drive with guards
    • Radiator, Package mounted.
  • Exhaust System
    • Exhaust manifold; dry
  • Fuel System
    • Fuel cooler
    • Primary fuel filter w/integral water separator and secondary filter, spin on
    • Integral Tank Base, 24 Hrs, UL142
    • Engine fuel transfer pump
    • Fuel priming pump
  • Generator Set
    • Complete system designed & built at ISO 9001:2000 certified facilities
    • Factory tested to design specifications at full load conditions
    • All protective devices and control functions simulated and checked
  • Generators And Generator Attachments
    • 6 leads
    • Voltage regulator (single phase sensing)
    • Easy access to AVR and terminals
    • Insulation, Class H
    • Brushless, self-excited 2/3 pitch (600V uses Internal Excitation)
    • Terminal Box, IP22 RHS Facing, Bottom Cable Entry
    • Standard winding protection for non-harsh environments with relative humidity ? 95%
    • IP23 protection
  • Governing System
    • Cat Electronic Governor (ADEM A4)
  • Lube System
    • Oil filler and dipstick.
    • Shallow oil pan.
    • Oil filter, spin on.
    • Oil cooler
    • Lubricating Oil, CK-4 (10W-30)
    • Oil drain with valve.
    • Fumes disposal to front of radiator.
  • Mounting System
    • Includes lifting provisions and termination points for coolant and lube oil drain lines
    • Captive linear vibration isolators between base and engine-generator
  • Protection
    • Safety Shutoff - High water temperature
    • Safety Shutoff - Overspeed
    • Safety Shutoff - Low Oil Pressure
  • Starting/charging System
    • 24V,45 amp charging alternator.
    • 24-volt electric starting motor.
  • General
    • Parts Book
    • Vibration damper.
    • Lifting Eyes
  • Air Inlet System
    • Air Cleaner (Non-Canister Disposable)
  • Bases, Mounting & Fuel Tanks
    • Audio & Visual Fuel Alarm (@90% Fuel Level)
    • Integral Tank Base, 24 Hrs, UL142
    • 5 gallon Spill Containment
    • Overfill Prevention Valve
    • Fuel Tank Fill Pipe & Lockable Cap
    • Wide Base - Skid
  • Circuit Breaker
    • 400A LSI
    • Auxiliary Contacts
    • 400A LS/I
    • 800A LSI
    • 600A LSI
    • 1200A LS/I
    • 800A LS/I
    • 600A LS/I
    • 1200A LSI
  • Control System
    • 20A GFCI (Ground Fault Circuit Interrupter)
    • Ground Fault Relay
    • 16 -light NFPA 99/110 Annunciator
    • Volt Free Contacts
    • Twist Release, Red Button Emergency Stop
    • 100A Load Center
    • Product Link Remote Monitoring hardware
    • Audible Alarm Gp
    • Earth (Ground) fault relay
    • Volt free contact
    • Remote E-Stop button
    • Discrete I/O module
    • Annunciators box
    • Local annunciator
  • Exhaust System
    • 8" Muffler - 25 dBA Attenuation
    • Flexible Exhaust Connection
    • Manifold & Turbocharger Guards
  • Generator
    • Space Heater
    • Permanent Magnet Generator
  • Starting System
    • Jacket Water Heater
    • Standard Battery Set: 1000 CCA, 90 amp/hr.
    • Battery Charger (UL Certified)
    • Oversize Battery Set, 1400 CCA, 200 amp/hr.
  • General
    • Extended Service Coverage
    • Generator Test Report
    • CSA Certification
    • UL2200 Certification
    • Tool set
  • Circuit Breakers
    • Single LSI motorised circuit breaker
    • Single LSI motorised Circuit Breaker
    • Auxiliary contacts
    • Neutral bar (208V)
  • Enclosures
    • E-Stop
    • Sound Attenuated Level 2 Enclosure (White)
    • AC & DC Source Lights
    • Sound attenuated enclosure
  • Cooling System
    • Coolant heater
    • Stone guards
    • Jacket water heater with pump
  • Base / Fuel Tank
    • Audio & visual fuel alarm
  • Fuel System
    • Integral 8 hr tank base
  • Starting And Charging
    • Oversize battery set
    • Standard battery set
    • 5 Amp battery charger
    • Battery disconnect switch
  • Certifications
    • CSA 22.2
    • UL2200 Listed
    • Seismic
  • Lube System
    • Manual sump pump
×