CG170 Gas Generator Set
Maximum Electrical Efficiency |
43.3% |
Maximum Standby Rating |
- |
Engine Model |
CG170 |
Continuous Rating |
1560 ekW @1.0pf |
Fuel Type |
Natural Gas, Biogas, Coal Gas |
Frequency |
50 or 60 Hz |
Gas Generator Sets Specification
Maximum Electrical Efficiency |
43.3% |
Maximum Standby Rating |
- |
Maximum Standby Rating |
- |
Generator Set Specifications
Continuous Rating |
1560 ekW @1.0pf |
Fuel Type |
Natural Gas, Biogas, Coal Gas |
Frequency |
50 or 60 Hz |
RPM |
1500 or 1800 rpm |
Maximum Electrical Efficiency |
43.30% |
Engine Specifications
Bore |
7 in |
Stroke |
8 in |
Displacement |
4,320 in³ |
Aspiration |
TA |
Engine Model |
CG170-16 |
Generator Set Dimensions
Length |
261 in |
Width |
70 in |
Height |
87 in |
Dry Weight - Genset |
32,849 lb |
High Efficiency, Lower Operating Costs
- Miller cycle timing with combustion chamber and spark plug improvement help on saving up to 15% fuel gas per year
- CG170 (non-miller) is optimized for Island-Mode capability
- Gearbox helps limit wear and tear on engine components, lowering operating costs and increasing availability
Low installation, Building and Operating Costs
- Extended maintenance intervals thanks to sooth-free combustion and enlarged oil tank
- Low fuel consumption due to improved combustion chamber and pre-chamber spark-plugs
- Flexible fields of application also with fluctuating gas qualities due to Total Electronic Management (TEM)
- Optimized oil management
Optimized Lubrication Consumption
- Consumes up to 1900 liter less lube oil per year than comparable models<li>
- Longer lubricant change and oil change intervals<li>
-
Air Inlet
- Turbocharger with a water-cooled bearing case for all cylinder
- One-element single-stage air cleaner with enclosure and sevice indicator
-
Control Panels
- TEM (Total Electronic Management)
-
Cooling
- Jacket water and SCAC thermostats
- Electrical jacket water and aftercooler coolant pump
- flange connections for JW inlet and outlet
- Cat flanges on SCAC circuit
-
Exhaust
- PEARL/Low resistence exhaust system
- Closed crankcase ventilation system
-
Fuel System
- Independently controlled cylinder monitoring and ignition system
- Pre-chamber spark plugs
- Electronic fuel metering valve
-
Generator
- Busbar connections
- Anti-condensation space heater
- closed-coupled generator result in no torque transmission to the base frame
- Winding temperature detectors
- Reactive droop
- 3-phase sensing and KVAR/PF control
- grid code generator
-
Starting/charging
- 24V starting motors
- Battery disconnect switch
-
General
- Crankshaft vibration damper and guard
-
Air Inlet
- Mounting stand
- Air cleaner with precleaner
-
Cooling
×