DG200-2 (3 phase)
Voltage |
120 / 208, 120 / 240, 277 / 480, 346 / 600 VAC |
Frequency |
60 Hz |
Natural Gas Rating |
200 eKW |
Speed |
1800 rpm |
Emissions/Fuel Strategy |
U.S. EPA Certified for Non-Emergency Application |
Engine Model |
14.2 L, Inline 6, 4 Cycle, Spark - Ignited |
Generator Set Specifications
Voltage |
120 / 208, 120 / 240, 277 / 480, 346 / 600 VAC |
Frequency |
60 Hz |
Natural Gas Rating |
200 eKW |
Speed |
1800 rpm |
Emissions/Fuel Strategy |
U.S. EPA Certified for Non-Emergency Application |
Fuel Type |
Natural Gas |
Displacement |
865 in |
Engine Specifications
Engine Model |
14.2 L, Inline 6, 4 Cycle, Spark - Ignited |
Fuel System |
Carburetor, Down Draft |
Compression Ratio |
9.5:1 |
Governor Type |
Electronic |
Aspiration |
Turbocharged-Aftercooled |
Bore |
5 in |
Stroke |
7 in |
Generator Set Dimensions
Length |
128 in |
Width |
53 in |
Height |
67 in |
Weight |
5,756 lb |
Engine
- Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight
Generator
- Matched to the performance and output characteristics of Cat engines
- Industry leading mechanical and electrical design
- Industry leading motor starting capabilities
- High Efficiency
EMCP Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Design Criteria
- The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
- Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water
UL 2200 / CSA - Optional
- UL 2200 Listed packages
- CSA Certified
- Certain restrictions may apply
- Consult with your Cat® Dealer
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
-
Cooling
- Closed coolant recovery system
- Factory-installed radiator
- 50/50 Ethylene glycol antifreeze
- Radiator and cooling fan complete with protective guards
- Standard ambient temperatures up to 50°C (122°F)
-
Air Inlet
- Single element air filter
-
Fuel
- Primary and secondary fuel shut-off
- Low fuel pressure switch
- Fuel pressure test po
- Natural Gas or LP Vapor
- NPT connection
- Dual lock off valves
-
Exhaust
- Exhaust outlet with 3” pipe
-
Generator
- Permanent magnet excitation
- Full load capacity alternator
- Class H insulation material
- Permanent magnet excitation
- Integrated Voltage Regulator
- Matched to the performance and output characteristics of Cat engines
- Class H insulation material
- Full load capacity alternator
- IP23 Protection
-
Controls
- EMCP 4.2 Series generator set controller
-
Mounting
- Vibration isolaton (puck type)
- Rubber vibration isolators
-
Electric Power - Package Serial Number Prefix
- Battery charging alternator
-
Electric Starting And/or Prelube
- Battery cables
- Solenoid activated starter motor
- Engine electrical system
- Solenoid activated starter motor
-
Governor
- Electronic governor (non adjustable)
-
Control Panel
- EMCP 4.2 Series generator set controller
-
Starting/charging
- Batteries with rack and cables
- 12 volt starting motor
-
Starting/charging
- Jacket water heater
- Battery heater
- Charging alternator
- Battery charger – UL Listed 10 amp
-
General
- Enclosures: sound attenuated, weather protective
- Suitable for Use as Service Equipment (SUSE)
- Automatic transfer switches (ATS)
- UL 2200 package
- CSA Certification
-
Generator
- Thermal magnetic or electronic trip MCCBs
- Anti-condensation heater
- Shunt trip and auxiliary contact breaker
- Anti-condensation heater
- Excitation: [ ] Permanent Magnet Excited (PM)
- Oversize and premium generators
×