Open transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II)
Product Features
Advanced safety with faster switching and no line voltages connected at the door
Voltage and frequency sensing of both sources and load
USB port to upload/download settings
Available Bluetooth connection and enhanced communication capabilities
Password protection color touchscreen HMI
Integrated help button and menu
Five programmed packages and IO
Contact wear monitoring including real-time status and predicted contact end-of-life
Fast controller response to outage recovery and fast switching (<50ms)
Control Panel
TruOne L4 - color touchscreen HMI compatible with Ekip Connect software, with standard programmable functions and IO, and fast controller response to outage recovery and fast switching (<50ms).
Functions
High current protection and alarm
Wide 200-480V range with auto-configuration of system settings for 100-1200A range
High time-based withstand and closing ratings (WCR)
Short-time withstand ratings in every frame (CBS, CBSD, and CBSCT models)
Standards
UL 1008, NFPA 70, 99, 101 and 110
NEMA ICS 10
cUL
Conducted and radiated emissions - CISPR 11:2009, Class A
ESD immunity test - IEC/EN 61000-4-2 Class B
Radiated RF, electromagnetic field immunity test - IEC/EN 61000-4-3 10 V/m
Electrical fast, transient/burst immunity test - IEC/EN 61000-4-4
Surge immunity test - IEC/EN 61000-4-5 0.5 to 2 kV
Conducted immunity test - IEC/EN 61000-4-6
Voltage dips and interruption immunity - IEC/EN 61000-4-11
Harmonic voltage immunity test - IEC/EN 6100-4-13
Control
Color touchscreen
Voltage and frequency settings: Pick up and Drop out
Time Delay Settings: Override momentary, Transfer, Generator stop, Center-OFF (Delayed Transition Type), Pre-transfer, Post-transfer, Elevator Pre-signal, Elevator Post-signal, and Load shead.
Source failure detections: No Voltage, Under/Over Voltage, Phase missing, Voltage unbalance, Invalid frequency, and Incorrect phase sequence