3412C | 750 ekW 60 Hz Generator Set

  • Exterior View

3412C | 750 ekW 60 Hz Generator Set

Maximum Rating 800 ekW
Minimum Rating 635 ekW
Emissions/Fuel Strategy Low BSFC
Voltage 220 to 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Generator Set Specifications
Maximum Rating 800 ekW
Minimum Rating 635 ekW
Emissions/Fuel Strategy Low BSFC
Voltage 220 to 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Prime
Standby Rating 750 ekW
Prime Power Rating 680 ekW
Engine Specifications
Engine Model 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore 5 in
Stroke 6 in
Displacement 1,649 in³
Compression Ratio 13:00:01
Aspiration TA
Fuel System Pump and Lines
Governor Type ADEM™ A5
Generator Set Dimensions
Length - Maximum 162 in
Width - Maximum 78 in
Height - Maximum 75 in
Dry Weight - Genset (minimum) 5,761 lb
Dry Weight - Genset (maximum) 13,275 lb

Cat Generator Set Package

        

  • Cat generator set packages have been fully prototype tested
  •     

  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

Designed to meet applicable global standards including ISO 8528, ISO 3046 and IEC 60034-1, with CE, UKCA and EAC conformity available depending on configuration and market.

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
  • Air Inlet System
    • Standard light duty air cleaner
  • Alternator
    • IE / PM Excitation
  • Base
    • Standard base
  • Control Panel
    • EMCP 4.2B
  • Cooling System
    • Coolant drain line with valve, piped to edge of base
    • Radiator with guard (Sized for 50 degrees C)
    • Coolant level shutdown
  • Governing System
    • Cat electronic governor
  • Mounting System
    • Linear vibration isolators
  • Starting / Charging System
    • 24V Starter motor
    • 45A Charging alternator
    • Standard battery with rack, cables
  • Telematics
    • Cat® Product Link™ PLE641 cellular
  • Exhaust System
    • 10, 35 dBA Mufflers
    • Elbow kit
    • Manifold and turbocharger guards
    • Manifold and turbocharger guards
  • Circuit Breakers
    • 3-Pole / 4-Pole, IEC 100% rated
  • Air Inlet System
    • Heavy duty air cleaner
    • Dual element air cleaners
    • Open element air cleaners
  • Certificates
    • Eurasian Conformity (EAC) mark
  • Starting / Charging
    • Oversize batteries
    • Battery chargers
    • Heavy duty starting system
  • Control Panel
    • Common alarm / Shutdown relay
    • EMCP 4.3
    • Local discrete I/O package
    • EMCP 4.4
  • Generator And Attachments
    • Anti-condensation heater
  • Base
    • 1200L fuel tank base
×