Cat generator set packages have been fully prototype tested
Accepts 100% block load in one step and meets NFPA 110 loading requirements
Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
Reliable, rugged, durable design
Field-proven in thousands of applications worldwide
Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
Superior motor starting capability minimizes need for oversizing alternator
Designed to match performance and output characteristics of Cat diesel engines
Robust Class H insulation
Cat Control Panel
User-friendly interface and navigation
Scalable system to meet a wide range of installation requirement
Expansion modules and site-specific programming for specific customer requirements
Cooling System
Designed to operate in standard ambient temperatures up to 50�C (122�F)
Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
EU Declaration of Conformity
EU Declaration of Incorporation
Eurasian Conformity (EAC)
One Safe Source
Components used in the generator set are selected at the design stage to provide optimum package performance
The generator set is fully assembled at a Caterpillar facility following our quality guidelines
Each generator set package is tested before leaving the Caterpillar facility
Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
Cat dealers have over 1,800 dealer branch stores operating in 200 countries
Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Air Inlet System
Air cleaner; single element canister type
Control System
Text alarm/event descriptions
Emergency stop pushbutton
IVR includes reactive droop capability
KVAR / PF modes
EMCP 4.2B
3 Phase voltage sensing
Generator mounted - rear facing
Generator set packages include:
24 Volt DC operation
Caterpillar's voltage regulator
RFI suppression
Environmental sealed front face
Limiter and exciter diode monitor
Min / max exciter
Controls:
Speed adjust
Alarm acknowledge
Auto/start/stop control
Engine cycle crank
Engine cool
Customizable screens
PLC functionality
Lamp test
Load histogram feature
Accessory module data link
Reverse power (kW) (32)
6 Customer programmable digital inputs
3 Phase
+/- 2% accuracy
High coolant temperature
0 True RMS AC metering
Programmable protective relaying functions:
Reverse reactive power (kVAr) (32RV)
Communications:
Generator phase sequence
Over/under voltage (27/59)
Overcurrent (50/51)
RPM
Number of I/O varies on options selected
Overspeed
Serial annunciator module data link
Low coolant temperature
4 Programmable relay outputs (Form A)
1 Programmable relay outputs (Form C)
3 Analog inputs
Over/under frequency (81 o/u)
Digital indication for:
Low coolant level
Failure to start (overcrank)
Cat connect
1 Programmable digital outputs
DC volts
Operating hours
Coolant temperature
Oil pressure (psi, kPa or bar)
Amps (per phase & average)
Power factor (per phase & average)
Frequency (Hz)
Volts (L-L & L-N)
kW (per phase, average & percent)
kVA (per phase, average & percent)
kVAr (per phase, average & percent)
Warning/shutdown with common LED indication of shutdowns for: Low oil pressure - High coolant temperature - Overspeed - Emergency stop - Failure to start (overcrank) - Low coolant temperature - Low coolant level -
Low oil pressure
kW-hr (total)
kVAr-hr (total)
Cooling System
ATAAC - 3516E package radiators shipped installed
Certified standard PGS provided
Exhaust System
Flanged faced outlet(s)
Dry exhaust manifold
Fuel System
Secondary fuel filters
Fuel cooler; not included with packages without radiator
Flexible fuel lines - shipped loose
General
Right hand servicing
Caterpillar yellow with high gloss black rails and radiator
SAE standard rotation
Flywheel and flywheel housing - SAE No. 00
Generator And Attachments
NEMA standard hole pattern
Medium voltage:
Anti-condensation space heater
NEMA Class H insulation system, Class H temperature rise at 40C ambient
(125C prime/150C standby)
Winding temperature detectors
High voltage:
Busbar connections, right side extension box, bottom cable entry
Form wound
Low voltage: Random wound - Internal excitation (IE) - Winding temperature detectors - NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby) - Busbar connections, top center mounted, top cable entry - NEMA standard hole pattern
6 Lead
Permanent magnet excitation (PMG)
3 Phase brushless, Salient pole
Class H insulation, Class F temperature rise at 40C ambient
(105C prime / 130C standby)
Governing System
ADEM A5
Literature
Parts book
Operation & Maintenance Manual
Lubrication System
Integral lube oil cool
Oil filter, filler and dipstick
Oil drain lines and valve
Gear type lube oil pump
Lubricating oil
Fumes disposal
Mounting System
Rails - Engine/generator/radiator mounting
Anti-vibration mounts (shipped loose)
Rubber anti-vibration mounts - shipped loose
Starting System
24 Volt electric starting motor
Battery disconnect switch
Battery and battery rack w/cables
45 Amp Charging alternator
Control System
EMCP 4.4
Air Inlet System
Single element filter
Dual element air cleaner
Cooling System
Standard ambient radiators
Water level switch gauges
Optional installed ATAAC radiators
Optional installed radiators
Coolant
Standard ambient ATAAC radiators
Crankcase System
Ventilation system
No explosion relief valves
Explosion relief valves
Exhaust System
Y Adapters
Fuel System
Fuel priming pumps (Tier 4) - Manual or electric
Primary fuel filter
General
Special paint (Colors other than Caterpillar yellow or high performance paints)
US aid emblem
Generators And Attachments
Space heater
Differential current transformers (DCT) 8.7 kV and 15 kV classes