3516E Low Voltage Generator Set
| Maximum Rating |
2750 ekW |
| Minimum Rating |
2500 ekW |
| Emissions/Fuel Strategy |
Tier 2, Low NOx |
| Voltage |
416 to 13,800 Volts |
| Frequency |
60 Hz |
| Speed |
1800 rpm |
Generator Set Specifications
| Maximum Rating |
2750 ekW |
| Minimum Rating |
2500 ekW |
| Emissions/Fuel Strategy |
Tier 2, Low NOx |
| Voltage |
416 to 13,800 Volts |
| Frequency |
60 Hz |
| Speed |
1800 rpm |
| Duty Cycle |
Standby, Mission Critical, Prime |
| Standby Rating |
2750 ekW |
| Prime Power Rating |
2500 ekW |
Engine Specifications
| Engine Model |
3516E, V-16, 4-Stroke, Water-Cooled Diesel |
| Bore |
7 in |
| Stroke |
8 in |
| Displacement |
4,765 in³ |
| Compression Ratio |
14.7:1 |
| Aspiration |
ATAAC |
| Fuel System |
EUI |
| Governor Type |
Adem™ A5 |
Generator Set Dimensions
| Length - Maximum |
312 in |
| Width - Maximum |
104 in |
| Height - Maximum |
132 in |
| Dry Weight - Genset (maximum) |
40,750 lb |
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
Cat ECS Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- UL 2200 Listed
- CSA
- IBC seismic certification
- OSHPD pre-approval
One Safe Source
- Components used in the generator set are selected at the design stage to provide optimum package performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
-
Air Cleaner
- Single element with service indicator
-
Starting
- Heavy duty electric starter(s)
-
Cooling
- ATAAC
- Standard Ambient Radiator
-
Crankcase Ventilation System
- Non filtered crankcase ventilation
-
Controller
-
Alternator
- Form wound
- Permanent Magnet Excitation
-
Telematics
-
Mounting System
-
Power Termination
-
Air Cleaner
- Dual element with service indicator
-
Muffler
- Industrial grade (15 dB)
- Critical grade (25 dB)
- Hospital grade (35 dB)
-
Starting
- Standard batteries
- Oversized batteries
- Air starter(s)
- Jacket water heater
-
Output Voltage
- 416V
- 480V
- 600V
- 4160V
- 12470V
- 13200V
- 13800V
-
Alternator Temperature Rise (over 40°c Ambient)
- 150°C
- 125°C/130°C
- 105°C
- 80°C
-
Alternator Attachments
- Anti-condensation space heater
- Stator and bearing temperature monitoring and protection
-
Power Termination
- Bus bar
- Circuit breaker
- 1600A
- 2000A
- 2500A
- 3000A
- 3200A
- 4000A
- 5000A
- IEC
- UL
- 3-pole
- 4-pole
- Manually operated
- Electrically operated
-
Trip Unit
-
Controller
-
Controller Attachments
- Local annunciator module
- Remote annuciator module
- Expansion I/O module
- Remote monitoring software
-
Charging
- Battery charger - 10A
- Battery charger - 20A
- Battery charger - 40A
- Battery charger - 50A
-
Cooling
- No Radiator
- High Ambient Radiator
-
Crankcase Ventilation System
- Filtered crankcase ventilation
- Closed filtered crankcase ventilation
-
Vibration Isolators
-
Telematics
-
Extended Service Terms
- 2 year (prime)
- 3 year
- 5 year
- 10 year
-
Extended Service Coverage
- Silver
- Gold
- Platinum
- Platinum plus
-
Ancilliary Equipment
- Automatic transfer switch (ATS)
- Paralleling switchgear
- Paralleling switchgear
- Paralleling controls
-
Certifications
- UL 2200
- IBC seismic certification
- OSHPD pre-approval
×