C2.2 | D25 Generator Set
| Standby Rating |
25.0 ekW |
| Frequency |
60 Hz |
| Emissions/Fuel Strategy |
US EPA TIER 4I (EPA 40 CFR Part 1039 Interim Tier 4) |
| Voltage |
480/277, 240/120, 208/120, 600/346, 240/120 VAC |
| Speed |
1800 rpm |
| Duty Cycle |
Standby |
Generator Set Specifications
| Standby Rating |
25.0 ekW |
| Frequency |
60 Hz |
| Emissions/Fuel Strategy |
US EPA TIER 4I (EPA 40 CFR Part 1039 Interim Tier 4) |
| Voltage |
480/277, 240/120, 208/120, 600/346, 240/120 VAC |
| Speed |
1800 rpm |
| Duty Cycle |
Standby |
| Prime Power Rating |
22.0 ekW |
| Minimum Rating |
15.5 ekW |
| Maximum Rating |
20.0 ekW |
Engine Specifications
| Engine Model |
Cat® C2.2, In-line 4, 4-cycle diesel |
| Bore |
3 in |
| Stroke |
4 in |
| Displacement |
134 in³ |
| Compression Ratio |
23.3:1 |
| Aspiration |
Turbocharged |
| Fuel System |
Mechanical Cassette Type |
| Governor Type |
Mechanical |
Generator Set Dimensions
| Length - Maximum |
89 in |
| Width - Maximum |
41 in |
| Height - Maximum |
58 in |
| Dry Weight - Genset (maximum) |
2,052 lb |
Cat C2.2 Engine
- Reliable, rugged, durable design
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
Alternator
Designed to match performance and output characteristics of Cat diesel engines
Industry leading mechanical and electrical design
GCCP 1.2 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
- Image may not be a representative of actual product
Cooling System
- Designed to operate in standard ambient temperatures up to 40°C (104°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Full range of attachments
- IP23 Alternators
- Anti-vibration mounts
- UL142 compliant
- 24, 48 and 72 hour fuel tanks with option of skid base
- Factory fitted telematics
Footprint
- Compact design allows for improved packaging, resulting in the smallest genset footprint
-
Engine
- Diesel Engine 2.2L, EPA TIER IV Interim
- Electrical system, 12 VDC
-
Exhaust System
-
Fuel System
- Actuator with electronic governor
-
Control Panel
- GCCP 1.2. R220 / R221 / D350 voltage regulators
-
Telematics
- PL444 Product link 4G LTE telematics
-
Generators And Generator Attachments
- Anti-condensation Space heaters
- M-Frame
-
Starting / Charging System
-
General
- Operation and maintenance manuals
- Parts book
- Paint - Caterpillar yellow except rails are gloss black
-
Air Inlet
-
Cooling System
-
Exhaust
- Exhaust expander
- Elbow, flange
- Flexible fitting
- Muffler and spark-arresting muffler with companion flanges
-
Telematics
- PLG 601 & 641 product link telematics
-
Enclosures
- Sound attenuated steel & aluminum enclosures
-
Mufflers
-
Starting / Charging System
- Charging alternator
- Jacket water heater
- Battery charger
- Space heaters
×